1. Teldor- CAT-7 網路線
    Teldor-CAT -6A電腦網路線
    Teldor-CAT -6電腦網路線
    回上一頁
  2. 產品搜尋
    分 類:
    關鍵字:  

    首頁 > > Teldor-CAT -6電腦網路線

    Teldor-750BZ24000 BUNDLE 6x(4x2x23 AWG Cat. 6 U/UTP) CAT6 24P 低煙無鹵網路線
    看原圖
    TELDOR-750BZ24000

    Teldor-750BZ24000 BUNDLE 6x(4x2x23 AWG Cat. 6 U/UTP) CAT6 24P 低煙無鹵網路線

    BUNDLE 6x(4x2x23 AWG Cat. 6 U/UTP)

    Part Number:
    750BZ24000
     

    Applications: Indoor Backbone, High bandwidth digital applications with low BER, High data rates, Interconnections in digital multiplex equipment
    General Construction:
    This is a bundle of six Cat. 6 (750BZ04xxx) cables.
    Each cable contains 4 twisted pairs, a special star shaped central filler, all cabled and jacketed with LSZH compound in U/UTP structure.
    The six cables, are cabled together with filler elements, and overall warpped with double tape.
    Outer Diameter: 20.2 mm nom.
    Weight: 314 kg/km
    Design & Materials
    Conductor Material: Bare Copper
    Conductor Size: 23 AWG
    Conductor Construction: Solid
    Insulation Material: PO
    Insulation O.D.: 1.0 mm nom.
    Conductor unit identification: Solid/stripe
    Color code: Per TIA/EIA 568-B
    Conductor unit lay-up: Pairs
    Inner Jacket Material: LSZH
    Inner Jacket Diameter: 6.7 mm
    Inner Jacket Color: Light Gray - or per request
    Total number of wires: 48
    Marking: Teldor Standard, Per request
    Standards
    Standards: IEC 61156, TIA/EIA-568
    Flamability Rating: IEC 60332-1, UL 1581 VW-1
    Performance
    Electrical Properties:  
    Cat. 6 Un-screened Pair Horizontal Cables*
     

    Freq.

    MHz

    Attenuation
    dB/100m
    20oC

    PS NEXT Loss
    dB

    NEXT Loss
    dB

    RL
    dB

    PS ELFEXT
    dB
    ELFEXT
    dB
    Typical
    Value

    Cat. 6

    Typical
    Value

    Cat. 6

    Typical
    Value

    Cat. 6

    Typical
    Value

    Cat. 6

    Typical
    Value

    Cat. 6

    Typical
    Value

    Cat. 6

    1

    2.0

    2.8

    75.0

    72.3

    78.0

    75.3

    22.0

    20.0

    90.0

    65.0

    93.0

    68.0

    4

    3.7

    3.8

    66.0

    63.3

    69.0

    66.3

    25.0

    23.0

    90.0

    53.0

    93.0

    56.0

    10

    5.7

    6.0

    60.0

    57.3

    63.0

    60.4

    28.0

    25.0

    80.0

    45.0

    83.0

    48.0

    20

    8.1

    8.5

    56.0

    52.8

    59.0

    55.8

    28.0

    25.0

    80.0

    39.0

    83.0

    42.0

    30

    10.0

    10.5

    53.0

    50.1

    56.0

    53.1

    27.0

    23.8

    70.0

    35.5

    73.0

    38.5

    100

    19.0

    19.9

    45.0

    42.3

    48.0

    45.3

    24.0

    21.1

    63.0

    25.0

    66.0

    28.0

    150

    23.6

    24.9

    43.0

    39.7

    46.0

    42.7

    22.0

    18.8

    60.0

    21.5

    63.0

    24.5

    200

    27.7

    29.1

    41.0

    37.8

    44.0

    40.8

    21.0

    18.0

    58.0

    19.0

    61.0

    22.0

    250

    31.4

    33.0

    38.0

    36.3

    41.0

    39.3

    20.0

    17.3

    55.0

    17.0

    58.0

    20.0


    *Supplied cables meet the minimum Cat. 6 transmission requirements as per IEC 61156-5 Ed. 2
     

     

    Frequency Range: 1 - 250 MHz
    Impedance: 100 Ω
    Coupling Attenuation: Type III
    DC Resistance: 73 Ω/km nom.
    Max. Resistance Unbalance: 2 %
    Capacitance Unbalance: 1.2 pF/m max.
    Velocity of Propagation: 68 % nom.
    Propagation Delay Skew: 35 ns/100m max.
    Dielectric Strength: 700 V/minute
    Min. Insulation Resistance : 5 GΩ•km
    Max. Tensile Strength - Short Term: 200 N
    Max. Operating Temperature: +60 °C
    Min. Operating Temperature: -40 °C